Tyco Sprinkler

Leading Wholesaler of tyco upright sprinkler, tyco pendent sprinkler and tyco side wall sprinkler from New Delhi.

Tyco Upright Sprinkler

REQUEST CALLBACK

Tyco Upright Sprinkler
Get Best Quote

Thanks for Contacting Us.

Approx. Rs 190 / PieceGet Latest Price

Product Details:
Temp Rating165 deg C
Frame Color CodeWhite, Blue
Maximum Working Pressure175 psi (12,1 bar)
Discharge CoefficientK=5.6 GPM/psi 1/2 (80,6 LPM/bar 1/2 )
Temperature RatingsRefer to Table A
FinishesSprinkler Refer to Table A Recessed
FrameBrass
Sealing ButtonBronze w/TEFLON
Ejection SpringStainless Steel
StrutMONEL
HookBronze/MONEL
DeflectorBronze
Fusible ElementSolder, Copper, Stainless Steel
Temperature165, 212, 280 deg C
Thread1/2",3/4"
ApprovalTY3111,TY3211,TY4111,TY4211,TY4811,TY4911
WrenchW9
Wrench RecessedW10
BrandTyco Fire Protection

The TYCO Series TY-L, 5.6 and 8.0 K-factor, Upright, Pendent,
and Recessed Pendent Sprinklers described in this data sheet are standard response, standard coverage, solder type spray sprinklers designed for use in light, ordinary, and extra
hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, chemical plants, etc. The recessed version of the Series TY-L Pendent Sprinkler, where appli-
cable, is intended for use in areas with a finished ceiling. It uses a two-piece Style 20 (1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon. The Recessed Escutcheon provides 1/4 in. (6,4 mm) of recessed adjustment or up
to 1/2 in. (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprin-
klers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently,it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of
ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum,
along with the corrosive nature of the chemical to which the sprinklers will be exposed.An intermediate level version of the
Series TY-L Pendent Sprinkler can be obtained by utilizing the Series TY-L Pendent Sprinkler in combination with the Model S Shield.

Notice:
The TYCO Series TY-L, 5.6 and 8.0 K-factor, Upright and Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition
to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these
devices.

The owner is responsible for main taining their fire protection system and devices in proper operating condition. Contact the installing contrac tor or product manufacturer with any
questions.

Design Criteria:
The TYCO Series TY-L, 5.6 and 8.0 K-factor, Upright, Pendent, and
Recessed Pendent Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency
(e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Prevention Data Sheets). Only the Style 20 or 30 Recessed Escutcheon, as applicable, are to be used for recessed pendent installations.

Features:
  • All hazards
  • Discharges a hemispherical water spray pattern in the area beneath the sprinkler
  • Designed for use in light, ordinary, and extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, chemical plants, etc.
Yes! I am Interested

View PDF

Tyco Pendent Sprinkler

REQUEST CALLBACK

Tyco Pendent Sprinkler
Get Best Quote

Thanks for Contacting Us.

Approx. Rs 185 / PieceGet Latest Price

Product Details:
BrandTyco
Maximum Working Pressure175 psi (12,1 bar)
Discharge CoefficientK = 2.8 GPM/psi 1/2 (40,3 LPM/bar 1/2 ), K = 5.6 GPM/psi 1/2 (80,6 LPM/bar 1/2 ), K = 8.0 GPM/psi
Frame MaterialBronze
Link Assembly MaterialNickel
Ejection SpringInconel
Button MaterialBronze
Seal MaterialTeflon
Tempature Rating165 deg F (74 deg C) U
Frame Color CodeUnpainted White
DeflectorBronze

The TYCO Series TY-FRL, 2.8, 5.6, and 8.0 K-factor, Upright and Pendent Sprinklers described in this data sheet are the quick response, standard coverage, solder type spray sprinklers designed for use in light and ordinary hazard commercial occupancies such as banks, hotels, shopping malls, schools, hospitals, etc.

The recessed version of the 2.8 and 5.6 K-factor, Series TY-FRL Pendent Sprin - kler, where applicable, is intended for use in areas with a finished ceiling. It uses a two-piece Style 20 (1/2 inch NPT) Recessed Escutcheon.The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush pen dent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut.An intermediate level version of the, "5.6 and 8.0 K-factor", Series TY-FRL, Pendent Sprinkler can be obtained by, utilizing the Series TY-FRL Pendent, Sprinkler in combination with the Model, "S4 Shield."

The Series T Y-FRL Sprinklers described herein must be installed
and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.

The owner is responsible for main taining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

Operation:
The fusible link (heat collector) assembly is comprised of two halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, allowing the sprinkler to operate.

Design Criteria:
The TYCO Series TY-FRL Pendent and Upright Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., ULListing is based on the requirements
of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Prevention Data Sheets). Only the Style 20 Recessed Escutcheon, as applicable, is to be used for recessed pendent
installations.

Installation:
The TYCO Series TY-FRL Sprinklers must be installed in accordance with this section.

A leak tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft./lbs. (9,5 to 19,0 Nm). A leak tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft./lbs. (13,4 to 26,8 Nm).

Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to make-up for insufficient adjustment in the escutcheonplate by under-or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. Series TY-FRL Pendent and Upright Sprinkler Installation The Series TY-FRL Pendent and Upright Sprinklers must be installed in accordance with this section.

Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklers are to be installed in the upright position.

Step.2 With pipe thread sealant applied to the pipe threads, hand
tighten the sprinkler into the sprinkler fitting.

Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 9 Sprinkler Wrench (Ref. Figure 6). With reference to Figures 1, 2, and 3, the W-Type 9 Sprinkler Wrench is to be applied to the wrench area.


Additional Information:

  • Item Code: TY-FRL2.8
Yes! I am Interested

View PDF

Tyco Pendent Sprinkler

REQUEST CALLBACK

Tyco Pendent Sprinkler
Get Best Quote

Thanks for Contacting Us.

Approx. Rs 185 / PieceGet Latest Price

Product Details:
BrandTyco
MaterialBrass
Temperature Rating165, 212, 280 deg C
Thread1/2, 3/4 inch

The TYCO Series TY-FRL, 2.8, 5.6, and 8.0 K-factor, Upright and Pendent Sprinklers described in this data sheet are a quick response, standard coverage, solder type spray sprinklers designed for use in light and ordinary hazard commercial occupancies such as banks, hotels, shopping malls, schools,
hospitals, etc. The recessed version of the 2.8 and 5.6
K-factor, Series TY-FRL Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses a two-piece Style 20 (1/2 inch NPT) Recessed Escutcheon.

The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut.

An intermediate level version of the 5.6 and 8.0 K-factor, Series TY-FRL Pendent Sprinkler can be obtained by utilizing the Series TY-FRL Pendent Sprinkler in combination with the Model
S4 Shield.

The Series T Y-FRL Sprinklers described herein must be installed
and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.

The owner is responsible for main taining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions.

Operation:
The fusible link (heat collector) assembly is comprised of two halves that are joined together by a thin layer of solder. When the rated temperature isreached, the solder melts and the two link halves separate, allowing the sprinkler to operate.

Design Criteria:
The TYCO Series TY-FRL Pendent and Upright Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Prevention Data Sheets). Only the Style 20 Recessed Escutcheon, as applicable,is to be used for recessed pendent
installations.
Yes! I am Interested

Tyco Side Wall Sprinkler

REQUEST CALLBACK

Tyco Side Wall Sprinkler
Get Best Quote

Thanks for Contacting Us.

Approx. Rs 210 / PieceGet Latest Price

Product Details:
BrandTyco

TYCO Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Hori-
Zontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) are decorative 3 mm glass bulb type spray sprinklers designed for use in hydraulically calculated sprinkler systems in
light hazard, commercial occupancies such as churches, restaurant seating areas, hotels, educational facilities, offices, etc. With their coverage up to 16 ft (4,9 m) wide by 24 ft (7,3 m) long, they are designed for installation along a wall or the side of a beam and
just beneath a smooth ceiling. Horizontal sidewall (HSW) sprinklers are commonly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across the ceiling is not desirable.

The fast response thermal sensitivity rating of the Series TY-FRB, 3 mm bulb type sprinklers provides for a quick response extended coverage (QREC) rating for many of the coverage areas detailed in Tables B and C.

 The recessed version of the Series TY-FRB Extended Coverage Horizontal Sidewall Sprinkler utilizes either a two-piece Style 10 (1/2 inch NPT) or Style 40 (3/4 inch NPT) Recessed Escutcheon with 1/2 in. (12,7 mm) of recessed adjustment or up to 3/4 in. (19,1 mm) of total adjustment from the flush sidewall position, or a two-piece Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT).

Recessed Escutcheon with 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush sidewall position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe lengths to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is
not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user is consulted with respect to the suitability of these coatings for any given
corrosive environment. The effects of ambient temperature, the concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the
chemical to which the sprinklers will be exposed.
Yes! I am Interested

 
X


Explore More Products

Contact via E-mail
Contact via SMS
Tripathi Hardware & Mill Store
Suraj Tiwari (Owner)
No. 2771, 1st Floor, Peepal Mahadev Hauz Qazi, Chandni Chowk,
New Delhi - 110006, Delhi, India
Call Us: 
Call Response Rate: 55%
Share Us :
F G T L



Home  |   About Us   |  Our Products  |  Site Map  |   Contact Us

© Tripathi Hardware & Mill Store. All Rights Reserved (Terms of Use)
Developed and Managed by IndiaMART InterMESH Limited

Tripathi Hardware & Mill Store